As a previous study showed, the voltage on a distribution line with high R/X ratio will actually decrease as shunt capacitance is added. This thesis develops a new distribution feeder model and confirms this unexpected result. Then the IEEE radial test feeders are modeled to further study the effect and provide additional insight into voltage control on feeders with high R/X ratio.