dc.identifier.citationPhase-change heat transfer of sintered-particle wick in downward facing orientation: Particle size and wick thickness effects. International Journal of Heat and Mass Transfer, vol. 155:art no. 119840en_US
dc.identifier.issn0017-9310
dc.identifier.urihttps://doi.org/10.1016/j.ijheatmasstransfer.2020.119840
dc.identifier.urihttps://soar.wichita.edu/handle/10057/17642
dc.descriptionClick on the DOI link to access the article (may not be free).en_US
dc.description.abstractTwo-phase cooling systems using wicks offer reliable and high heat flux cooling capability, however, the maximum heat removal capacity is related to capillary pumping limit and wick superheat. In this study, non-uniform wicks are examined to simultaneously enhance the capillary pumping limit and minimize wick superheat. The non-uniform wick consists of a thin evaporation wick for reducing the wick superheat and a thick coolant supply wick for enhancing the coolant supply. Also, it has a phase-separating wick attached to the coolant supply wick to ensure the vapor escape channels. The thin wick is fabricated using sintered-copper particles with 30–200 μm spherical particles, while the post and phase-separating wicks are constructed using 10 and 3 layers of 200 μm copper particles, respectively. To minimize the gravity-driven liquid supply, the liquid reservoir is placed below the wick structure, i.e., downward facing orientation. The heat flux is measured as a function of the wick superheat using different particles sizes and thicknesses of the thin wick, i.e., 30, 60, 100, 200, 60/200, and 100/200 μm with 1–3 layers. The results show that 60 μm particles result in the minimal wick superheat at q < 100 W/cm2 for 1 and 2 layers of the wick, while the 100/200 μm particles with 3 layers leads to the maximum heat flux of 223 W/cm2, which is ~48% enhancement compared to the bare copper surface at the wick superheat of 38.6 °C. Also, it is found that the 2 and 3 layer wicks substantially decrease the wick superheat compared to the single layer wick, although the wick thickness (conductive thermal resistance) is larger. This is attributed to the 2 and 3 layer wick enhance the liquid supply, by increasing the cross-section area of the wick, thus, delaying the surface dryout.en_US
dc.language.isoen_USen_US
dc.publisherElsevieren_US
dc.relation.ispartofseriesInternational Journal of Heat and Mass Transfer;v.155:art no.119840
dc.subjectWick structureen_US
dc.subjectCapillary limiten_US
dc.subjectThermal performanceen_US
dc.subjectHeat fluxThermal resistanceHeat transfer coefficienten_US
dc.subjectThermal resistanceen_US
dc.subjectHeat transfer coefficienten_US
dc.titlePhase-change heat transfer of sintered-particle wick in downward facing orientation: Particle size and wick thickness effectsen_US
dc.typeArticleen_US